Work

Incorporation of self-commutating CSC transmission in power system load-flow

Year: 2005
Type: conference-paper
Abstract: — This paper presents a method which incorporates self-commutated CSC transmission directly in a fast decoupled Newton-Raphson a.c. load flow. The d.c. equations are presented in a per unit form that is compatible with the per unit a.c. equations. A sequential method of solution is adopted in solving the load flow equations. The a.c. system equations are solved with the d.c. system modelled simply as a real and reactive power injection at the terminal busbar and for a d.c. solution, the a.c. system is modelled simply as a constant voltage at the converter a.c. terminal busbar. Further the new load flow program is tested for its effectiveness by carrying out several test cases.This paper presents a method which incorporates self-commutated CSC transmission directly in a fast decoupled Newton-Raphson a.c. load flow. The d.c. equations are presented in a per unit form that is compatible with the per unit a.c. equations. A sequential method of solution is adopted in solving the load flow equations. The a.c. system equations are solved with the d.c. system modelled simply as a real and reactive power injection at the terminal busbar and for a d.c. solution, the a.c. system is modelled simply as a constant voltage at the converter a.c. terminal busbar. Further the new load flow program is tested for its effectiveness by carrying out several test cases. 1.
Language: English
Open Access status: green
OpenAlex ID: W1487475397
FWCI:
Cites: 2
Cited by:
Related to: 10