Work

Improvement of Compact Heat Exchangers with Inclined Louvered Fins

Year: 1984
Type: article
Abstract: A simple theoretical model is proposed for flow patterns around the louvers of compact heat exchangers in air-conditioners. The purpose of this paper is to determine the louver arrangement having the highest heat transfer coefficient and the lowest static pressure drop. Experiments using a scaled-up modeling technique employing thermistor plates point to the existence of a specific fin configuration and louver angles that bring forth optimum heat transfer and static pressure drop characteristics. Performance of a newly-designed, inclined louvered fin and a flat tube heat exchanger was clarified using a steady state hot water-to-air testing technique. The heat transfer coefficient and static pressure drop of an optimally inclined louvered heat exchanger is 16% higher and 2127% lower than those for conventional louvered heat exchangers.
Language: English
Open Access status: diamond
OpenAlex ID: W1988185362
FWCI: 1.676
Cites: 2
Cited by: 25