A technique for estimating transmission line fault locations from digital impedance relay measurements
Year: 1988
Type: article
Abstract: A technique is presented that is suitable for estimating locations of shunt faults. The estimates are reasonably accurate even if the fault resistance is substantial and the transmission line is connected to energy sources at both terminals. The technique uses post fault fundamental-frequency voltages and currents measured at the two line terminals. The measurements need not be synchronized, and the source impedances are not used by the estimation procedure. The mathematical development of the technique is presented. Sample test results using simulated fault data are included.>
DOI: 10.1109/61.4237
Authors: M.S. Sachdev, R. Agarwal
Institution: University of Saskatchewan
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green