Year: 2015
Type: article
Abstract: This paper presents a new control strategy for high voltage direct current (HVDC) transmission based on the synchronverter concept: the sending-end rectifier controls emulate a synchronous motor (SM), and the receiving end inverter emulates a synchronous generator (SG). The two converters connected with a DC line provide what is called a synchronverter HVDC (SHVDC). The structure of the SHVDC is firstly analyzed. It is shown that the droop and voltage regulations included in the SHVDC structure are necessary and sufficient to well define the behavior of SHVDC. The standard parameters of the SG cannot be directly used for this structure. A specific tuning method of these parameters is proposed in order to satisfy the usual HVDC control requirements. The new tuning method is compared with the standard vector control in terms of local performances and fault critical clearing time (CCT) in the neighboring zone of the link. The test network is a 4-machine power system with parallel HVDC/AC transmission. The results indicate the contribution of the proposed controller to enhance the stability margin of the neighbor AC zone of the link.
Institutions: National Engineering School of Tunis, École Centrale de Nantes, École Normale Supérieure Paris-Saclay, Centre National de la Recherche Scientifique, Laboratoire des Sciences du Numérique de Nantes, Laboratoire des systèmes et applications des technologies de l'information et de l'énergie, Université de Nantes, Nantes Université
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W2092676196