A building survey for asbestos fallout
Year: 1977
Type: dissertation
Abstract: A modern sixteen-story office building was surveyed to determine if erosion of spray asbestos fibres from the cementitious surface of the air plenum chambers was contaminating the building air supply system, subjecting the occupants to a potential hazard. The NIOSH approved method of collection and analysis was utilized. This consisted of collecting the fibres on a membrane filter, dissolving the filter on a glass slide, and then counting the fibres utilizing phase microscopy. Fibre concentrations were found to be extremely low and most probably reflect the general ambient level in the urban environment, as two nearby buildings that did not incorporate asbestos-based building materials had comparable levels. These extremely low levels do not appear to be biologically significant.
Author: Marc H. Axelrod
Institution: California State University, Northridge
Language: English
Subfield: Pulmonary and Respiratory Medicine
Field: Medicine
Domain: Health Sciences
Open Access status: green
OpenAlex ID: W2135003274