Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Year: 2010
Type: conference-paper
Abstract: Condensation heat transfer performance of louvered fin-and-flat-tube heat exchanger (FTHX) in single slab and in residential air-conditioning system were experimentally investigated, and were compared with fin-and-circular-tube heat exchangers (CTHX) under the same testing conditions.The test results showed that: FTHX had the characteristics of low pressure drop of air side, high pressure drop of refrigerant side and less refrigerant charge; the overall heat transfer performance of copper FTHX was higher than that of 7mm CTHX but a little lower than that of 9.52mm CTHX; the cooling capacity and EER of the residential air-conditioning system with FTHX were a little lower than those of the system with 9.52mm CTHX.Original Tube 9.52×0.