Work

Effect of sensor location on controller performance in a wastewater treatment plant

Year: 2013
Type: conference-paper
Abstract: Complete mixing is hard to achieve in large bioreactors in wastewater treatment plants.This often leads to a non-uniform distribution of components such as e.g.dissolved oxygen and the process rates depending on them.Furthermore, when these components are used as input for a controller, the location of the sensor can potentially affect the control action.In this contribution, the effect of sensor location and the choice of setpoint on the controller performance were examined for a non-homogeneous pilot bioreactor described by a compartmental model.The impact on effluent quality and aeration cost were evaluated.It was shown that a dissolved oxygen controller with a fixed setpoint performs differently as function of the location of the sensor.When placed in a poorly mixed location, the controller increases the aeration intensity to its maximum capacity leading to higher aeration costs.When placed just above the aerated zone, the controller decreases the aeration rate resulting in lower dissolved oxygen concentrations in the whole system, compromising effluent quality.In addition to the location of the sensor, the selection of an appropriate setpoint also impacts controller behavior.This suggests that mixing behavior of bioreactors should be better quantified for proper sensor location and controller design.
Language: English
Subfield: Pollution
Open Access status: green
OpenAlex ID: W2298040720
FWCI:
Cites: 4
Cited by:
Related to: 10