Adiabatic air dehumidification in laminar flow desiccant matrices
Year: 1987
Type: article
Abstract: Adiabatic step transient heat- and mass-transfer and pressure drop experimental data were obtained for a dehumidifier test matrix that contained microbead-silica-gel desiccant in a parallel-plate geometry. The data were analyzed and compared with the results of two other test dehumidifiers: a parallel-plate matrix using crushed silica gel, and a staggered, parallel-strip matrix using microbead silica gel. The analysis showed that the overall heat- and mass-transfer Nusselt numbers of the staggered, parallel-strip matrix were about 70% to 80% larger than those of the parallel-plate matrices. It also showed that the solid-side resistance to moisture diffusion in the smaller microbead silica gel was about 45% less than that of crushed silica gel because the particle size was 60% smaller. The ratio of heat- or mass-transfer coefficient to pressure drop of the microbead-silica-gel staggered, parallel-strip matrix was higher than the other two test dehumidifiers. Based on these findings, a dehumidifier using microbead silica-gel in a staggered, parallel-strip geometry can be made more compact than the other combinations. 15 refs., 9 figs., 5 tabs.
Author: A. Pesaran
Language: English
Subfield: Mechanical Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
Funder: U.S. Department of Energy
Award: G5143245769
OpenAlex ID: W2299412677