Work

Impedance-traveling wave assembled algorithm of one-terminal fault location for transmission lines

Year: 2010
Type: article
Abstract: In order to advance the reliability and accuracy of one-terminal fault location for transmission lines,an impedance-traveling wave assembled algorithm,which combines measurement impedance method with traveling wave method,is presented. It uses method based on measurement impedance to calculate roughly fault distance. Then,time regions of reflected waves from fault point and opposite bus to detective bus are confirmed respectively through the distance. Finally,exact time of reflected wave from fault point and that of reflected wave from opposite bus to detective bus are identified respectively in corresponding regions,and fault location is implemented according to the results detected. It has complementarities of both methods,because measurement impedance method guarantees reliability and traveling wave method improves accuracy. The simulation has proved that the assembled algorithm proposed is correct.
Author: Na Huang
Language: Chinese
Open Access status: diamond
OpenAlex ID: W2348714816
FWCI:
Cites:
Cited by: 2
Related to: 10