Identification of grounding fault using Gradient-Closing transform
Year: 2011
Type: article
Abstract: Whether the power distribution network is on land or ship , the single-phase ground faults account for the largest proportion. In the HRG power grid, when intermittent arc grounding or cable metallic single discharge appeares, grounding resistance will not only fail to suppress over-voltage, but also can increase the fault current. Based on the single-phase fault experiment, this paper proposes a method of using the Gradient Transform and Closing transform cascade to identify the types of ground fault. This method can separate metal grounding and intermittent arc grounding, and ignore the situation of the single discharge. Using experiment and simulation to verify the method, it is found the method has good ability to identify the fault under different conditions.
Author: Jia Liu
Language: Chinese
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: diamond
OpenAlex ID: W2365532465