Study and improvement of DC filter protection
Year: 2011
Type: article
Abstract: The principle of DC filter protection and configuration of Gaozhao and Xingan HVDC projects in China southern power grid is introduced. Then DC filter C1 unbalance protection and capacitor C1 overload protection are studied through fault cases and the reasons of the maloperation are found. The paper proposes an improved scheme considering positive-negative when the real value of ITD/ITS is compared with setting value aiming at capacitor C1 unbalance protection. With respect to capacitor C1 overload protection,the protection blocking when UdL exceeds 170%is presented to avoid the maloperation caused by abnormality of DC line voltage measurement system. The simulation results and on-site operation show that the improved techniques presented are effective and feasible.
Author: Quan Zhou
Institution: China Southern Power Grid (China)
Language: Chinese
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Keywords: HVDC, protection maloperation