EHV transmission line faulty phase selection scheme based on backward Prony algorithm
Year: 2011
Type: article
Abstract: Component analysis of EHV transmission line fault transient signals based on distributed parameter shows that the amplitude and the frequency of high frequency transient current signals after fault can reliably distinguish various fault types. So a faulty phase selection scheme based on high frequency transient current signals after fault is proposed. In this scheme,backward Porny algorithm and QR decomposition are employed,which makes the extraction of HF component more accurate and fast.A large number of ATP simulation results show that the proposed scheme can distinguish different fault types fast and correctly and it is not affected by transition resistances,inception angles,and load current.
Author: Mingyu Yang
Language: Chinese
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: diamond
OpenAlex ID: W2383172461