Fast algorithm of branch contingency ranking based on voltage vulnerability

Year: 2010
Type: article
Abstract: A fast algorithm of contingency ranking based on voltage vulnerability is proposed.The critical value in post-fault system is fast gotten by linear sensitivity.Then the definition of static energy margin is elicited based on the relations of static energy with power injection and bus voltage,and two indices for evaluating voltage vulnerability in contingency screening and ranking are proposed,one of which is local index,and the other one is whole index. The local index calculates the energy margins of nodes under contingency on stable operation,and takes the value of the weakest node as the energy margin of system.The whole index is the energy margin of total energy under contingency on stable operation.The critical contingencies can be gained after contingency screening and ranking based on the two indices.The effectiveness of the proposed method is demonstrated through comparing with interior point method on IEEE30-and IEEE57-bus system.