Gap protection setting of the 110 kV main transformer and research of the operation
Year: 2009
Type: article
Abstract: Combined with the frequent issue that the earth faults occur on the local 110 kV power line and then the main transformer CB trip off because the gap protection operates at the line end,it detailedly analyzes the gap protection settings and the coordination issues for the 110 kV line protection,and gives some advices for the protection configurations.Practicallys it chooses the gap distance for the transformer neutral point,the settings of the gap current protection and the improvements for the protection coordination.