Improvement of current protection method for ultra short incoming line and feeder on switching station

Year: 2010
Type: article
Abstract: The modern urban power networks have large short-circuit capacity,and the cables are used for incoming line and feeder on load dense district’s switching station,so electric distance is very short. In general,three-stage current protection can not ensure selectivity and sensitivity. The principle of instantaneous current protection delay time interlock is developed,when line is fault,the instantaneous current protection relay is interlocked by lower protection relay,which can ensure the protection’s selectivity. The issue of protection in switching station incoming lines and feeders is solved. The device has been developed and applied in practice,the principle is correct and the issue that the ultra short lines instantaneous protection has not selectivity is solved.