Work

Photovoltaic Ground Fault Simulations Using SPICE.

Year: 2013
Type: article
Abstract: In order to b etter understand the impact of changing the fuse ratings on ground fault protection devices (GFPDs) of photovoltaic (PV) arrays with regard to detection window and nuisance tripping, a range of fault scenarios, including array size, leakage current, fault position, and fault impedance were analyzed using a simulated program with integrated circuit emphasis (SPICE).The simulations show that, by decreasing GFPD ratings, there is an improvement in the number of faults that can be detected without increasing the number of nuisance trips and, therefore, the GFPD ratings mandated by UL1741 should be decreased in the future.
Language: English
Open Access status: green
OpenAlex ID: W2531160239
FWCI:
Cites: 4
Cited by: 3
Related to: 10