Analisis Intensitas Pencahayaan Di Ruang Kuliah Gedung Fisika Universitas Jember Dengan Menggunakan Calculux Indoor 5.0b
Year: 2016
Type: article
Abstract: The purposes of this research is to assess the illuminating of inclassroom 35C 201 40 and 35C 210 40 phycics building University of Jember. Data retrieved by using a lux meter, with three times the measurement at everypoint. After data was obtained from calculation, so the data will be enteredinto Software Calculux Indoor 5.0b. Based on the research that has been done,it showed that in classroom 35C 201 40 and 35C 210 40 not in accordancewith the standard set by Indonesian National Standard of 250 lux, with result79,59 lux and 77,05 lux. Whereas the result of the measurement andcalculation of the reflectances values on both the classroom to the walls, floor,and ceiling has been corresponding of Indonesian National Standardrecommendations with a value from 0.5 until 0.8. In accordance with thetheory of illumination for Indonesian National Standard must full fil thecriteria: cleanliness of the room, the installation of the armature and the lightevenly, giving the bright color of the walls, floors, and ceilings. The simulationresult from Software Calculux Indoor 5.0b that is the illuminations atclassroom 35C 201 40 better than 35C 210 40. The illumination in bothclassroom not in accordance with the standard set by Indonesian NationalStandard, so that it can affect of the learning process.
Source: JURNAL PEMBELAJARAN FISIKA
Language: Indonesian
Subfield: Building and Construction
Field: Engineering
Domain: Physical Sciences
SDG: Quality education
Open Access status: diamond