Abstract: Various applications require dry air at low temperature, such automation equipment, semiconductor manufacturing, chemical production lines, and coating processes for the shipbuilding industry. Four evaporators for low temperature (below $0^{\circ}C$) were installed for a dehumidification system. Moist air is cooled sequentially over three evaporators. The first evaporator has an evaporation temperature of $13^{\circ}C$, that of the second evaporator is $5^{\circ}C$, and that of the third evaporator is maintained at $-1.3^{\circ}C$. In the fourth evaporator implantation thereby the moisture contained in the moisture air. A pressure regulator (CPCE 12) is used at this point and is defrosted when the vapor pressure is below a set value. The non-implantation moisture of the air is a heating system that uses the waste heat of a condenser with high temperature. It develops the cooling type's dehumidifier, which is important equipment that prevents the destruction of protein and measures the temperature and humidity at each interval by changing the front air velocity from 1.0 m/s to 4.0 m/s. The cooling capacity was also calculated. The greatest cooling capacity was 1.77 kcal/h for a front air velocity of 2.0 m/s