Year: 2011
Type: conference-paper
Abstract: Outdoor air ventilation is a key mechanism controlling the airborne spread of several diseases. However, ventilation guidelines for hospitals are not typically based on preventing infection transmission. Aim: We sought to assess the effectiveness of current ventilation rates on infection risks for influenza, tuberculosis (TB) and rhinovirus within three distinct rooms in a major tertiary hospital in Australia. Methods: The rooms targeted were a Lung Function Laboratory, negative pressure isolation room in the Emergency Department and an Outpatient Consultation Room. Air exchange measurements were performed in each by using CO2 decay, and the proportion of outdoor air supplied was determined by CO2 mass-balance at the air handling unit. Gammaitoni and Nucci's infection risk model, based on the traditional Wells-Riley model, was then employed to model scenarios typical of those experienced by patients. Results: Current outdoor air exchange rates in the Lung Function Laboratory and Isolation Room were appropriate, and infection risks for all modelled scenarios were <3.6%. Influenza risk for patients entering the OPD Room after an infectious patient departed ranged from 3.6 to 20.7% depending on the occupancy time of the susceptible and infectious patient. Conclusions: In the absence of definitive guidelines, air exchange measurements combined with modelling afford a useful means of assessing, on a case-by-case basis, the suitability of room ventilation at preventing airborne transmission.
Language: English
Subfield: Pulmonary and Respiratory Medicine
Field: Medicine
Domain: Health Sciences
Open Access status: green
OpenAlex ID: W2750855458