Measurement and simulation of fire smoke BRANDFORSK PROJEKT 702-041 031

Year: 2005
Type: report
Abstract: The arson fire at the Växjö psychiatric hospital in 2003, in a tragic way demonstrated the importance of knowing how materials will behave when ignited.The ignitability of a PUR-based mattress proved to be the initiator for a fast and intensive flash-over where the PVC floor carpet played an important part.This was shown in a reconstruction made at SP where the PVC-material also explained the very high smoke density reported.The findings where confirmed by soot samples taken at the hospital as they contained high amounts of chlorides.As the PUR-material will produce isocyanates when heated, the soot samples taken were also analysed with regards to these substances but no trace of isocyanates were found.However, isocyanate-metabolites where found in lung-tissues from both death victims.The reconstruction and another full-scale experiment where a mattress was burnt were in the project both compared to CFD-based simulations.In the mattress case, an advanced flamelet-model was used for calculating the chemical composition of the gas, where as in the reconstruction, small-scale data was used as input for gas composition.The small-scale data was obtained using a suggested ISO-method for measuring smoke composition in various ventilation conditions.The method is based on a "Purser furnace", which was constructed as part of the project.
Language: English
Open Access status: green
OpenAlex ID: W2804613009
Cites: 7
Cited by: 9
Related to: 10