Abstract: This document is a contribution to improve the quality of electrical energy in the distribution network. In this article we will present a method that allows us to clean up in a very considerable way the electrical network of both harmonics and inter harmonics provoked, basically by the ultrafast switches used when controlling a PWM inverter supplying a three-phase asynchronous motor. We notice that this method can be generalized for other loads creating inter-harmonics. This proposed method was simulated using the MATLAB/SIMULINK software and had given remarkable results (there is a considerable reduction in total harmonic distortion (THD) of source current from 29.52% to 0.82%)
Language: English
Open Access status: diamond
OpenAlex ID: W2991216647
FWCI: 0.086
Cites: 25
Cited by: 1