Energy Savings With Solid-state Ballasts in a V.a. Hospital
Year: 1981
Type: article
Abstract: More than two hundred solid-state fluorescent ballasts were installed in representative areas of a Veterans Administration Hospital in Long Beach, California, to determine the cost-effectiveness of such an installation.The power and illumination levels in the test sites were measured first as they initially existed.then after the fixtures were cleaned and relamped with energy-saving fluorescent lamps, and finally a~ter the core-coil ballasts were replaced with solid-state ballasts.The annual energy savings for the complete retrofit was measured as 33.9%.In the director~s suite natural daylight was used to supplement the electrical illumination, providing an additional 2Q-25% energy savings.Thus, in that area, the total annual energy savings amounted to 48%.Al•l of the measured basis of life-cycle presented on sets of data are analyzed on the costing.The analyses are curves relating the costeffective price of a ballast to the cost of electrical energy.
Language: English
Field: Energy
Domain: Physical Sciences
Open Access status: green
Award: G660437508