Abstract: The losses in transformers, as defined in the Standardization Rules of the American Institute of Electrical Engineers, Sections 157-159, are as follows:157 MOLECULAR MAGNETIC FRICTION AND EDDY CURRENTS measured at open secondary circuit, rated frequency, and at rated voltage -I r, where I = rated current, r = resistance of primary circuit.158 RESISTANCE LosSES, the sum of the 12 r losses in the primary and in the secondary windings of a transformer, or in the two sections of the coil in a compensator or auto-transformer, where I = rated current in the coil or section of coil, and r = resistance.159 LOAD LossEs, i.e., eddy currents in the iron and especially in the copper conductors, caused by the current at rated load.For practical purposes they may be determined by short-circuiting the secondary of the transformer and impressing upon the primary a voltage suffi- cient to send rated load current through the transformer.The loss in the transformer under these conditions, measured by wattmeter, gives the load losses + 12 r losses in both primary and secondary coils.