Work

Assessment of the impact of HTSCs on superconducting fault-current limiters. [High Temperature SuperConductors (HTSCs)]

Year: 1993
Type: conference-paper
Abstract: The possible impact of nitrogen-cooled superconductors on the desip and cost of superconducting fault-current limiters is assessed by considering the technical specifications such devices must meet and by comparing material properties of 77-K and 4-K superconductors. The main advantages of operating superconductors at 77 K are that the refrigeration operating cost is reduced by a factor of up to 25 and the refrigeration capital cost is reduced by a factor of up to 10. The heat capacity is several orders of magnitude Larger at 77 K and at 4 K. This phenomenon increases conductor stability against flux jumps but makes switching from the superconducting to the normal state slow and difficult. Therefore, a high critical current density, probably at least 10[sup 5] A/cm[sup 2], is required.
Language: English
Open Access status: green
OpenAlex ID: W350179645
FWCI:
Cites:
Cited by:
Related to: 10