LSQ DC 123 IIR Algorithm for Unit Differential Protection Restraint and Generator Ground Fault Detection
Year: 2009
Type: article
Abstract: Izvornoznanstveni članak U radu je prikazan LS� DC 123 IIR algoritam, razvijen na Fakultetu elektrotehnike i računarstva Sveučilišta u Zagrebu, koji je dobiven iz originalnog LS� IIR algoritma.Glavna namjena algoritma je blokada numeričkih zaštitnih uređaja pri magnetiziranju energetskih transformatora spojenih u bloku s generatorom i stopostotna zaštita generatora od zemljospoja.Analiziran je rad LS� DC 123 IIR algoritma te je prikazano učinjeno poboljšanje u odnosu na LS� algoritam koji je u praktičnim uvjetima neupotrebljiv.LS� DC 123 IIR algoritam računa istosmjernu komponentu signala te amplitude prvog, drugog i trećeg harmonika iz mjerenih valnih oblika napona i struja.Uz amplitudne vrijednosti algoritam daje i fazne, kao što su kutovi osnovnog, drugog i trećeg harmonika između svih mjerenih valnih oblika električnih signala.Iz algoritma je također moguće dobiti i vremensku konstantu istosmjerne prigušujuće komponente koja se javlja pri kratkom spoju.Iz dobivenih vrijednosti se donose zaključci prema tome je li nastupio kvar ili je potrebno blokirati proradu numeričke zaštite bloka generator-transformator. LSQ DC 123 IIR Algorithm for Unit Differential Protection Restraint and Generator Ground Fault DetectionOriginal scientific paper The LS� DC 123 IIR algorithm, developed at Faculty of Electrical Engineering and Computing University of Zagreb, derived from the original LS� IIR algorithm is discussed in the paper.The main purpose of the algorithm is digital protection relay restraint during the energisation (inrush current) of unit transformer and 100 % generator ground fault protection.The operation of LS� DC 123 IIR algorithm is analyzed and the obtained improvement is presented in relation to LS� algorithm, which is totally useless in practice.The LS� DC 123 IIR algorithm is used in extracting amplitude of DC component and amplitudes of fundamental, second and third harmonics from measured current and voltage waveforms.The algorithm also calculates phase angles between all measured current and voltage waveforms.If the time constant of decaying DC component is needed it is also available from algorithm.Based on algorithm output values decisions are made whether digital protection relays should trip or if restraint of unit generator transformer differential protection is necessary.
Authors: Juraj Havelka, Ante Marušić, Marko Delimar
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W352147355