Estimation of Sparkover Rate of Medium-Voltage Line Due to Indirect Lightning Hit Taking account of Statistics on Return-stroke Current
Year: 2006
Type: article
Abstract: The authors have developed a method of analysis of induced voltages where the Agrawal's model is adopted as a field-to-line coupling model. In this letter, the sparkover rate of a power distribution line associated with indirect hits is investigated based on numerical calculations taking account of statistics on return-stroke current. It turns out that the sparkover rate associated with a subsequent stroke is higher than that associated with a first stroke when the line is equipped with surge arresters.
Authors: Yasuji Hongo, Koji Michishita, Masaru Ishii
Language: English
Subfield: Astronomy and Astrophysics
Field: Physics and Astronomy
Domain: Physical Sciences
Open Access status: bronze