Work

Influence of the source elevation on a pool fire in a forced ventilated enclosure

Year: 2022
Type: conference-paper
Abstract: In nuclear facilities, fires can spread until reaching the upper part of a closed and mechanically ventilated compartment. In this area of the room, the fire sources are under-oxygenated, but lie in an environment with significant radiative heat flux. Previous studies dealt with elevated fires, and results showed that source elevation affects two phenomena: the combustion process and the flows inside the room. The present study aims to understand the effects of elevation on the fire dynamic in a special ventilation configuration: fresh air inlet in the lower part of the compartment, and vitiated air exhaust in the upper part. A series of tests was carried out in a reduced-scale apparatus, with a 0.09 m diameter pan filled with dodecane liquid fuel and placed at various heights. Two aspects were analyzed: the mass loss rate (MLR) and the gas temperature inside the room. First of all, the experimental results confirm the coupled and antagonistic effects of decreasing oxygen concentration and increasing temperature on the mass loss rate that were already highlighted in the literature. In addition, these results also show the role played by the flame height on the change in the combustion regime. Finally, the vertical temperature stratification is much more pronounced when the fire is elevated until it reaches a maximum height. Beyond this limit, stratification starts to disappear.
Source: HAL
Language: English
Open Access status: green
OpenAlex ID: W4286828049
FWCI:
Cites: 20
Cited by:
Related to: 10