Work

Arc-Fault Unwanted Tripping Survey with UL 1699B-Listed Products.

Year: 2020
Type: article
Abstract: Since adoption of the 2011 National Electrical Code®, many photovoltaic (PV) direct current (DC) arc-fault circuit interrupters (AFCIs) and arc-fault detectors (AFDs) have been introduced into the PV market.To meet the Code requirements, these products must be listed to Underwriters Laboratories (UL) 1699B Outline of Investigation.The UL 1699B test sequence was designed to ensure basic arc-fault detection capabilities with resistance to unwanted tripping; however, field experiences with AFCl/AFD devices have shown mixed results.In this investigation, independent laboratory tests were performed with UL-listed, UL-recognized, and prototype AFCl/AFDs to reveal any limitations with state-of-the-art arcfault detection products.By running AFCIs and stand-alone AFDs through realistic tests beyond the UL 1699B requirements, many products were found to be sensitive to unwanted tripping or were ineffective at detecting harmful arc-fault events.Based on these findings, additional experiments are encouraged for inclusion in the AFCFAFD design process and the certification standard to improve products entering the market.
Language: English
Open Access status: green
OpenAlex ID: W4297943151
FWCI:
Cites: 8
Cited by:
Related to: 10