Impact of Water Mist on Fire Extinguishment in Mechanically Ventilated Compartment as a Function of Airflow Rate
Year: 2023
Type: conference-paper
Abstract: This study demonstrates how or whether an inlet vent rate affects flame suppression behaviour in highly confined and mechanically ventilated installations which are a typical hazard in the nuclear safety area.The primary objective of the present work is to provide a detailed experimental study on water mist fire suppression phenomena in a buoyant, turbulent diffusion flame representing the key characteristics of a realistic fire.The present work focuses on water mist application in a hot confined environment from flame, smoke and hot enclosure walls, which allows to achieve maximum droplet evaporation.It is indicated that reduction in flameto-wall radiation heat transfer via cooling of smoke layer by water over liquid surface does not allow suppression of a confined fully developed fire because the mist can't transported to the fire source during the fire-water interaction period.Through the analysis on HRR, gas temperature, heat flux and chemical species, it is found that in a hot environment, a consecutive efficient cooling of the smoke layer thanks to a strong droplet evaporation leads to the fire suppression only with ACPH (Air Change Per Hour) below 28 via lack of oxygen.
Source: HAL
Institution: Institut Pprime
Language: English
Subfield: Safety, Risk, Reliability and Quality
Field: Engineering
Domain: Physical Sciences
Open Access status: green
OpenAlex ID: W4391422201