Safety and reliability assessment of CO2 refrigeration system for underground applications below -50 °C
Year: 2024
Type: article
Abstract: A new CO2 refrigeration concept is evaluated to cool the ATLAS and CMS experiments installed close to 100 m underground, at the Large Hadron Collider (LHC) at CERN. The first prototype unit produced to validate the conceptual design and to assess safety and reliability of the system has been commissioned. This paper presents results obtained, discusses the safety and reliability of the system and discourses on the list of recommendations for the future final units to cover the cooling loads of 380 kW for ATLAS and 750 kW for CMS at -53 °C evaporation temperature.
Source: Refrigeration Technology
DOI: 10.17816/rf635386
Authors: Pierre Barroca, Bart Verlaat, Daniella Teixeira
Language: English
Subfield: Mechanical Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: hybrid
OpenAlex ID: W4402355365