A simulation-based optimization of heat pump air circulation evaporating separation system for saline wastewater treatment
Year: 2024
Type: article
Abstract: Recycling salt and water from saline wastewater is crucial for environmental preservation, resource conservation, and social economy sustainability. The heat pump air circulation evaporating separation (HP-ACES) system for saline wastewater treatment is proposed. Nevertheless, it is discovered that the system evaporation efficiency ( SEE ) is low and solid crystalline salt does not precipitate during the experiment. Therefore, an established and validated mathematical model of the HP-ACES system is provided and the average relative errors of the system evaporation rate ( SER ) and SEE are 5.3 % and 7 %, respectively. The theoretical analysis of the non-optimized system indicates that the main cause of the low SEE of the HP-ACES system during the test is incorrect cooling water flow. Hence, the system optimization scheme is presented and the comparison of the HP-ACES system's performances before and after optimization is conducted. Results demonstrate that the SEE of the optimized HP-ACES system has been greatly improved (optimized system: 0.62–2.46 kg/kWh, non-optimized system: 0.77–0.91 kg/kWh). Additionally, there is almost no change in the yield and composition of the solid crystalline salt when the inlet air temperature of spray separation tower is above 90 °C.