Work

Joint optimal PMU and DULR placement in distribution network considering fault reconstruction and state estimation accuracy

Year: 2024
Type: article
Abstract: Due to the rapid development of the distribution network, there is an urgent need for high-precision state estimation and safe and stable operation, this paper proposes a joint optimal placement method for PMU and DULR in distribution networks considering fault reconstruction and state estimation accuracy. The proposed method aims to minimize the cost of PMU and DULR configuration. Based on the known pseudo-measurements and SCADA measurements, we use the E-optimal standard design of the state estimation error covariance matrix to form the state estimation accuracy index and take the relay protection function of FTU device and DULR device into consideration of the fault reconstruction. By solving the mixed integer semidefinite programming (MISDP) model, the optimal placement result is obtained, so that the network under normal condition and the network after multiple fault reconstruction can meet the constraints of state estimation accuracy and load loss rate respectively. The proposed method is tested on IEEE 33-node, 123-node systems as an example. The experimental results show that the proposed method is effective and practical.
Language: English
Open Access status: gold
Estimated APC paid: $3,500
OpenAlex ID: W4403739961
FWCI: 0.72
Cites: 34
Cited by: 7
Related to: 10