The Effect of Local and Interarea Oscillations of Wind Turbine Generators Based on Permanent Magnet Synchronous Generators Connected to a Power System
Year: 2024
Type: article
Abstract: : In this study, the effects of wind turbine generators (WTGs) based on permanent magnet synchronous generators (PMSGs) on oscillations of the power system are investigated. The analysis studies were performed for three different cases (base case, WTG based on PMSG displacement with a suitable synchronous generator, and WTG based on PMSG connection to a suitable bus without changing the synchronous generators) in Kundur’s two-area power system and the IEEE 30-bus test system. It has been concluded that WTG based on PMSG can have positive and negative effects on power system oscillatory stability depending on the value of synchronous generator power replaced by WTG based on PMSG power and the location of WTG based on PMSG.Cite this article as: C. Haydaroğlu, B. Yıldırım, H. Kılıç and M. Temel Özdemir, “The effect to local and interarea oscillations of a wind turbine generators based on PMSG connected to a power system,” Turk J Electr Power Energy Syst. 2025; 5(1), 41-53.
Institutions: Dicle University, Bingöl University, Fırat University
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: bronze
OpenAlex ID: W4404499666