Impact of the power-controlled static synchronous machine on transient stability of power system
Year: 2024
Type: article
Abstract: Compared with the grid-following (GFL)-converter-interfaced generations (CIG), the power-controlled static synchronous machine (PCSSM) can realize voltage and frequency control through the power tracking function, which has the potential to improve the transient stability of the power system. However, the evolution trend of transient stability of power systems with integrated power-controlled static synchronous machine is still unknown. This paper studies the transient stability characteristic of power systems after replacing synchronous generators (SGs) with the PCSSM. The PCSSM and GFL-CIG are integrated into the New England IEEE 39-bus test system, respectively. Firstly, we compare the transient stability of the PCSSM-integrated system with the GFL-CIG-integrated system by changing Converter-interfaced generation’s integration proportions and locations. Then, the impact of equivalent inertia coefficient J and damping coefficient D on the transient stability of the PCSSM-integrated system is analyzed. Finally, the advantages of PCSSM compared to GFL-CIG are compared and summarized.
Source: Frontiers in Energy Research
Authors: Liu Qing, Zhang Zheren, Xue Yicheng, Xu Zheng
Institution: Zhejiang University
Language: English
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $2,795