Abstract: Combining buildings into districts aggregates the diverse peak loads from individual buildings to improve the sizing of new energy supply systems.The non-simultaneity of peak loads (both electric and thermal) is evaluated using simultaneity factors.The simultaneity factor is the maximum of the district load profile divided by the maximum of the individual load profile.As the simulation of individual buildings works very well, this publication aims to present algorithms that calculate the combined load profile of district buildings from individual building load profiles using the simultaneity factor.Four different methods are presented for this purpose: (Mean) linear scaling of the load profile to a constant mean value, (Ref. P.) scaling to a reference load profile, (N. D.) normal distribution of the load profile to the neighboring time steps and (N. D. Ref.) normal distribution of the difference between the individual building load profiles and a reference profile to the neighboring time steps.All methods take a predetermined simultaneity factor into account to smooth the maximum load peak until this simultaneity factor is met.All methods are applied to measured electrical and thermal load profiles, and the calculation accuracy is compared.The results show that linear scaling to a reference profile model has the lowest errors.The normal distribution models lead to the lowest fluctuations.