Study on the Broadband Measurement Method of Electric Field Sensing Voltage Based on the Add-Window Technique
Year: 2024
Type: article
Abstract: With the popularization of power electronic equipment, the problem of harmonic pollution has become more and more prominent, posing a serious threat to the safe operation of power systems. In order to improve the stability and efficiency of the power system, the broadband measurement of harmonics has become a key direction of research. In this paper, a novel broadband harmonic measurement method is proposed, which combines the electric field sensing technique and the TCW add-window discrete Fourier transform technique. The amplification gain coefficient deviation of the measurement system is less than 3 dB in both steady-state and transient excitation signal test experiments. The measurement system can maintain a stable and continuous output in a wide frequency band within the range of MHz, which can effectively detect the harmonic components and provide an effective technical means for the monitoring of harmonics in the power system.
Source: Energies
DOI: 10.3390/en17246289
Language: English
Topic: Power Quality and Harmonics
Subfield: Electrical and Electronic Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $2,955
OpenAlex ID: W4405374812