Work

CO 2 ‐ and PM 2.5 ‐Focused Optimal Ventilation Strategy Based on Predictive Control

Year: 2025
Type: article
Abstract: This study developed and evaluated an optimal ventilation strategy for variable air volume (VAV) systems, targeting carbon dioxide (CO 2 ) and particulate matter less than 2.5 μ m in diameter (PM 2.5 ) concentrations. The strategy integrates system‐level demand‐controlled ventilation (DCV) based on real‐time occupancy data and zone‐level predictive control using indoor air quality (IAQ) prediction models. By predicting indoor CO 2 and PM 2.5 levels for the subsequent time step and dynamically adjusting control priorities, optimal airflow is determined. A co‐simulation model integrating EnergyPlus, CONTAM, and Python was employed for model training and testing. The proposed strategy was compared with on–off control, CO 2 predictive control, and PM 2.5 predictive control, demonstrating superior prediction accuracy and stable IAQ maintenance. The optimal ventilation strategy achieved the highest performance, maintaining CO 2 and PM 2.5 levels below their respective upper limits of 100% and 97.33% of the time. Although this strategy resulted in slightly higher energy consumption compared to the other control algorithms due to its multivariable control approach, it effectively maintained IAQ standards. This method simplifies development and maintenance by circumventing the need for complex optimization, providing a flexible and cost‐effective solution for IAQ management. Future research will focus on developing integrated VAV system control strategies that ensure comfort year‐round, addressing both energy efficiency and thermal comfort.
Source: Indoor Air
Language: English
Open Access status: hybrid
Estimated APC paid: $2,490
OpenAlex ID: W4406152999
FWCI: 3.877
Cites: 45
Cited by: 9
Related to: 10