Abstract: The rapid rise in inverter-based renewable resources has heightened concerns over subsynchronous resonance and oscillations, thereby challenging grid stability. This paper reviews approaches to identify and mitigate these issues, focusing on frequency scanning methods for stability assessment. It categorizes white-, black-, and gray-box modeling techniques, compares positive-sequence, dq-frame, and alpha-beta domain scanning, and examines perturbation shapes like step, ramp, and chirp. A comparative study highlights their strengths, limitations, and suitability for specific scenarios. By summarizing past events and surveying available tools, this work guides operators and researchers toward more effective, reliable stability analysis methods in grids with high renewable penetration.
Authors: Das, Shuvangkar Chandra, Saravana, Lokesh, Vu, Le Minh, Bui, Manh, Vu, Tuyen, Zhang, Jianhua, Ortmeyer, Thomas