Parametric study and thermal sensitivity analysis of a triple effect absorption refrigeration system
Year: 2025
Type: article
Abstract: Absorption refrigeration systems represent an efficient means of cooling utilizing waste heat, with triple-effect absorption refrigeration systems outperforming their double and single-effect counterparts in terms of efficiency. This study conducts energy and exergy analyses on a triple-effect absorption refrigeration system, focusing on internal heat balance and thermal sensitivity to maximize efficiency. The analysis pinpointed the most sensitive thermal sensitivity areas within the system, highlighting the high-pressure condenser (HPC) outlet and medium-pressure condenser (MPC) outlet as critical points. Notably, increasing the temperatures of HPC and MPC leads to enhanced COP and ECOP, with a mere 5 K rise in HPC exit temperature resulting in a remarkable 57 % boost in system performance. Similarly, elevating the MPC operating temperature by 5 K yields a significant 34 % improvement in COP value.
Authors: Kenan Saka, Mehmet Fatih Orhan
Institutions: Bursa Uludağ Üni̇versi̇tesi̇, American University of Sharjah
Language: English
Subfield: Mechanical Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $1,620
Funder: American University of Sharjah