Work

Short Circuit Fault Detection in DAR Based on V-I Characteristic Graph and Machine Learning

Year: 2025
Type: article
Abstract: Dry-type air-core reactors (DAR) are critical components in power systems but are prone to inter-turn short circuit faults which interrupt the symmetry of the winding structure. Inspired by the online detection of transformer winding deformation, the V-I method has been adapted to diagnose short circuit faults in reactors. However, the diagnostic criteria and thresholds of V-I method remain unclear. This paper presents a novel method for determining the threshold for detecting inter-turn short circuit faults in DAR, integrating V-I analysis with machine learning techniques. Specifically, Gradient Boosting Regression (GBR) is used to compute a standard diagnostic criterion value, and curve fitting is also used to define the threshold for identifying inter-turn short circuit faults. The experimental results demonstrate that this method effectively identifies fault conditions in DAR.
Source: Symmetry
Language: English
Open Access status: gold
Estimated APC paid: $2,896
OpenAlex ID: W4408620873
FWCI: 0.227
Cites: 15
Cited by: 1
Related to: 10