Abstract: ABSTRACT Grounding grid corrosion is one of the main reasons that affect the stable operation of electrical equipment in substations and endanger personal safety. After many years of operation, the grounding conductors will be eroded by soil. It may even cause major accidents and economic losses. Therefore, it is of great significance to diagnose the corrosion faults of the grounding grid and find out the corroded conductors. In this paper, the genetic K‐means algorithm (GKA) is proposed to solve the mathematical model and judge the corrosion of grounding conductors. This algorithm combines GA's global searching ability and K‐means's local searching ability, which improves the diagnosis result. In the simulation experiment, compared with the single GA's diagnosis, the diagnosis results of GKA were improved, and the number of misdiagnosed branches decreased by 66.7%. The simulation results show that the proposed algorithm takes less time to run, can eliminate the misdiagnosed branches commendably, and improve the accuracy of diagnosis. The proposed method provides a new idea to evaluate the corrosion degree of the grounding grid. The clustering algorithm is used to classify branches with similar corrosion degrees to achieve the purpose of corrosion diagnosis.
Institution: Foshan University
Language: English
Open Access status: gold
Estimated APC paid: $2,780
OpenAlex ID: W4409560169
FWCI: 1.901
Cites: 30
Cited by: 5