Work

Numerical analysis and experimental research on Acoustic-vibration characteristic of 110 kV transformer tank

Year: 2025
Type: article
Abstract: A vibroacoustic coupling model of the 110 kV transformer tank is constructed by using the finite element method. The structural vibration response under 100 Hz and 200 Hz sound source excitation is analyzed. Radiated sound field characteristics and sound transmission loss performance across the 0-400 Hz frequency range are evaluated. Then, a test system is established to measure vibration response and sound transmission loss through experiments. Simulation analysis and experimental test results show that the average sound transmission loss of the 110 kV transformer tank ranges from 30 dB to 40 dB. The simulation calculation results show good agreements with experimental test results, which prove the correctness of the vibroacoustic coupling model of the 110 kV transformer tank.
Authors: Dan Gang, Ma Jiangang, Qiu Ning, Wei Xiaolong, Zhao Yalin, Song Wenjin
Language: English
Open Access status: diamond
OpenAlex ID: W4410390652
FWCI:
Cites: 7
Cited by:
Related to: 10