Research on Stability of Transmission Tower Slopes with Different Slope Ratios Under Rainfall Conditions and Reinforcement Effects of Anti-Slide Piles
Year: 2025
Type: article
Abstract: With the extensive construction of high-voltage power grid projects in complex mountainous terrains, rainfall-induced slope instability poses a significant threat to the safety of transmission tower foundations. This study focuses on a power transmission and transformation project in Huizhou City, Guangdong Province. Using MIDAS GTS NX 2019 (v1.2), an unsaturated seepage-mechanics coupling model was established to systematically investigate the influence of slope ratios (1:0.75, 1:1, and 1:1.25) on slope stability under rainfall conditions and the reinforcement effects of anti-slide piles. The results demonstrate that slope ratios significantly govern slope responses. For steep slopes (1:0.75), post-rainfall matrix suction loss reached 43.2%, peak displacement attained 74.49 mm, and the safety factor decreased by 12.5%. In contrast, gentle slopes (1:1.25) exhibited superior stability. Anti-slide piles effectively controlled displacement growth (≤9.15%), but pile bending moments increased markedly with steeper slope ratios, accompanied by a notable expansion of the plastic zone at the slope toe. The study reveals a destabilization mechanism characterized by “seepage–strength degradation–displacement synergy” and recommends engineering practices adopting slope ratios of 1:1–1:1.25, combined with anti-slide piles (spacing ≤ 1.5 m) and dynamic drainage measures. These findings provide critical guidance for the design of transmission tower slopes in mountainous regions.
Source: Buildings
Authors: Guoliang Huang, Xiaolong Huang, Caiyan Lin, Ji Shi, Xiongwu Tao, Jiaxiang Lin, Bingxiang Yuan
Language: English
Subfield: Safety, Risk, Reliability and Quality
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $3,137
Award: G5656819990
OpenAlex ID: W4411353142