Work

Optimal PMU Placement based on Voltage Stability Index for Observability of Network

Year: 2025
Type: article
Abstract: This work presents a voltage stability Index (FLVSI) for optimal PMU placement (OPP) to achieve complete network observability. Every PQ bus is considered in the FLVSI strategy to attain weak PQ bus from PMUs are conditioned to allocate at weak PQ buses using ILP approach to attain observability of network. Zero Injection (ZIB) modeling is introduced to minimize PMU places in the network. The redundancy Index (RI) is formulated to compute redundancy for all buses in the network. IEEE –14 -39 and 118- bus networks are programmed in MATLAB and compared with standard techniques to present their efficacy.
Language: English
Open Access status: diamond
OpenAlex ID: W4411459154
FWCI:
Cites: 16
Cited by:
Related to: 10