Effect of cable sheath termination on transient overvoltages due to high-frequency cable-transformer resonance
Year: 2025
Type: article
Abstract: High-frequency resonances in cable-transformer systems can result in excessive overvoltages, increasing the probability of insulation failure for critical components such as power transformers. These resonances occur due to the interaction between the cable and transformer and are influenced by the cable’s characteristics, including the length and wave propagation velocity. In addition, the terminating impedances of the cable’s core and sheath conductors affect the resonance characteristic of the cable as well. Applying single-point sheath grounding to the high-voltage cable connecting the switchgear to the power transformer is conventional. This paper demonstrates that the cable-transformer resonances and resulting overvoltages can vary significantly depending on the end at which the sheath conductors are grounded. An in-depth investigation of such effects is carried out through rigorous mathematical analysis, followed by experimental validation and simulations in an electromagnetic transient (EMT)-based software using models that properly represent the equipment behaviors in a wide-frequency range. The results indicate that sheath conductor grounding configuration can profoundly affect the system response, influencing the severity of transient overvoltages caused by cable-transformer resonances.