Variable Dimensional Bayesian Method for Identifying Depth Parameters of Substation Grounding Grid Based on Pulsed Eddy Current
Year: 2025
Type: article
Abstract: The substation grounding grid, as the primary path for fault current dissipation, is crucial for ensuring the safe operation of the power system and requires regular inspection. The pulsed eddy current method, known for its non-destructive and efficient features, is widely used in grounding grid detection. However, during the parameter identification process, it is prone to local minima or no solution. To address this issue, this paper first develops a pulsed eddy current forward response model for the substation grounding grid based on the magnetic dipole superposition principle, with accuracy validation. Then, a variable dimensional Bayesian parameter identification method is introduced, utilizing the Reversible-Jump Markov Chain Monte Carlo (RJMCMC) algorithm. By using nonlinear optimization results as the initial model and introducing a dual-factor control strategy to dynamically adjust the sampling step size, the model enhances coverage of high-probability regions, enabling effective estimation of grounding grid parameter uncertainties. Finally, the proposed method is validated by comparing the forward response model with field test results, showing that the error is within 10%, demonstrating both the accuracy and practical applicability of the proposed parameter identification method.
Source: Energies
DOI: 10.3390/en18174649
Authors: Xiaofei Kang, Zhiling Li, Jie Hou, Su Xu, Yanjun Zhang, Zhihao Zhou, Jingang Wang
Institution: Chongqing University
Language: English
Subfield: Mechanical Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $3,137
OpenAlex ID: W4413908491
