Lightning Flashover Characteristic and Effective Protection Measures of 10 kV Distribution Line Network
Year: 2025
Type: article
Abstract: Among various failure causes, lightning overvoltage represents the most significant threat to overhead distribution lines, which serve as critical components in power systems. This study uses the hybrid partial element equivalent circuit (PEEC) multi-conductor transmission line (MTL) method to perform overvoltage simulations and investigate lightning risk distribution along distribution lines developed from a real 10 kV distribution networks in Guizhou, China. The results of the rocket-triggered lightning observation verify the accuracy of the hybrid method for direct lightning simulation. Combining the Monte Carlo method with the electro-geometric model (EGM), the impact of differential protection configurations on annual lightning flashover rates is analyzed. The results demonstrate that lightning strikes on phase wires generate high-magnitude overvoltages but with limited spatial influence, resulting in fewer pole flashovers. Conversely, strikes on poles produce lower overvoltage peaks but affect wider areas, leading to significantly more flashovers. Using annual flashover rates as the risk evaluation metric, the line topologies into high-risk, medium-risk, and other low-risk areas are classified. Targeting an annual flashover rate below 0.4 as the design objective, the configuration schemes of the arresters are progressively optimized. This risk-based approach provides an effective reference framework for differential protection design of distribution line safeguards.
Source: Energies
DOI: 10.3390/en18195097
Language: English
Subfield: Astronomy and Astrophysics
Field: Physics and Astronomy
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $3,137
Funder: China Southern Power Grid
OpenAlex ID: W4414512526