Investigation of the Impact of XLPE Cable Ageing on Impedance Mismatch Characteristics and Unbalanced Behaviour in Hybrid Operation Systems

Year: 2025
Type: article
Abstract: ABSTRACT In the Hainan–Guangdong interconnection project, oil leakage in oil‐filled cables required replacing the faulty core with a single core from a three‐core cross‐linked polyethylene (XLPE) cable, leading to mixed operation of XLPE and oil‐filled cables. However, systematic quantitative analysis on the three‐phase unbalance caused by differences in material parameters between the two cable types is lacking. This study focuses on the mixed operation system, using a real‐time digital simulation platform to build power flow and current distribution models. Finite element thermal analysis and accelerated thermal ageing experiments were conducted to reveal the evolution of XLPE cable insulation dielectric parameters during ageing. Two evaluation indices, the impedance mismatch coefficient and the length mismatch coefficient, were proposed to quantify how material degradation worsens system unbalance. Results show that after 1440 h of ageing, the system's negative‐sequence and zero‐sequence unbalance increased by 24.4% and 28.7%, respectively. A critical impedance mismatch threshold is identified; once exceeded, unbalance escalates and the system's stability margin diminishes. This research provides theoretical support for recognising ageing‐induced sequence impedance mismatch and related unbalance effects in hybrid submarine cable systems and lays a foundation for optimising operational stability and designing compensation strategies.
Source: High Voltage
Language: English
Open Access status: gold
Estimated APC paid: $2,200
OpenAlex ID: W4414622653
FWCI:
Cites: 24
Cited by:
Related to: