Work

Thermal Performance of Borehole Heat Exchangers with Varying Borehole Depths in Cold Regions: Implications from In Situ Thermal Response Tests

Year: 2025
Type: article
Abstract: In cold regions, performance reduction in a Ground-Coupled Heat Pump (GSHP) system has been frequently reported. Many operational strategies have been adopted to mitigate such an undesirable phenomenon. However, these strategies have limited effects because the specific heat rate of Borehole Heat Exchangers (BHEs) is usually treated as constant. In this study, eight BHEs were installed in typical loess areas in Northwestern China to investigate how borehole depth affects its thermal performance. Thermal response tests (TRTs) showed that deeper boreholes led to a higher fluid outlet temperature. Compared to 150 m and 100 m boreholes, the energy coefficient factor (η) for a 200 m borehole increased by 18.02% and 45.0%, respectively. Numerical simulation also confirmed that deeper BHEs perform better. In addition, the initial ground temperature influences the thermal performance sensitively, but in the opposite way for heating and cooling modes. These findings offer valuable insights for installing GSHP systems to achieve sustainable and high thermal performance in cold regions.
Source: Energies
Language: English
Field: Energy
Open Access status: gold
Estimated APC paid: $3,137
OpenAlex ID: W4415457916
FWCI: 0.279
Cites: 22
Cited by: 2
Related to: