SISO admittance reshaping and enhanced robustness of single-phase grid-connected inverter based on frequency-decoupling in weak grid
Year: 2025
Type: article
Abstract: Asymmetric control often introduces frequency coupling in single-phase phase-locked loop (PLL) under weak grid condition, which deteriorates the stability for the gridconnected system. In this paper, in order to address the infinite characteristics of frequency coupling in the single-phase system, an admittance model based on harmonic transfer function matrix is established. Then, by designing a decoupling factor in the current loop of the inverter, a reduced-order single-input singleoutput (SISO) admittance model is established. Furthermore, based on the improved model, an effective admittance shaping method is proposed to realize the passivity of output admittance, which ensures the stable operation of grid-connected inverter under weak grid condition. Finally, experimental results validate the effectiveness of the proposed method in suppressing frequency coupling and stability enhancement.
Institution: Wenzhou University
Language: English
Subfield: Control and Systems Engineering
Field: Engineering
Domain: Physical Sciences
Open Access status: gold
Estimated APC paid: $3,920
Award: G8174248076
OpenAlex ID: W4415555031
